Schneider Electric ATS22C14Q Soft starter, Altistart 22, ATS22 control 220V power 230V(37kW)/400...440V(75kW)
Code: SCHATS22C14Q
Unit of measure:
EACH
Description
SOFT STARTER ELECTRONIC 75KW 220V CONTR
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Product destination | asynchronous motors |
| Relative humidity | 0-95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| [Us] rated supply voltage | 230...440 V - 15...10 % |
| Discrete input voltage | 24 V <= 30 V |
| Operating position | vertical +/- 10 degree |
| Electromagnetic compatibility | electrostatic discharge level 3 conforming to IEC 61000-4-2 |
| Ambient air temperature for operation | 40-60 °C (with current derating 2.2 % per °C) |
| Connector type | 1 RJ45 |
| Minimum switching current | 100 mA at 12 V DC (relay outputs) |
| Noise level | 56 dB |
| Supplier ref | ATS22C14Q |
| Installed device | 31 |
| Motor starter type | soft starter |
| Supplier Code | ATS22C14Q |
| Component name | ATS22 |
| Supply voltage limits | 195-484 V |
| Ambient air temperature for storage | -25-70 °C |
| Discrete output type | relay outputs R2 230 V running- alarm- trip- stopped- not stopped- starting- ready C/O |
| Network frequency | 45...66 Hz |
| Power dissipation in W | 82 W for standard applications |
| PTC probe input | 750 Ohm |
| Vibration resistance | 1.5mm (f= 2-13 Hz) conforming to IEC 60068-2-6 |
| Communication data link | serial |
| Discrete input number | 3 |
| Network number of phases | 3 phases |
| Function available | internal bypass |
| Protection type | thermal protection: starter |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Motor power kW | 75 kW 440 V |
| Device connection | to the motor delta terminals |
| Communication port protocol | Modbus |
| IP degree of protection | IP00 |
| Range | Altistart 22 |
| Assembly style | with heat sink |
| Pollution degree | level 2 conforming to IEC 60664-1 |
| Output current | 0.4...1 Icl adjustable |
| Power range | 55-100 kW at 380-440 V 3 phases |
| Product specific application | pumps and fans |
| Control circuit consumption | 20 W |
| Factory setting current | 131 A |
| IcL starter rating | 140 A for connection in the motor supply line for standard applications |
| Discrete input logic | positive logic LI1- LI2- LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V- >= 5 mA |
| Depth | 229.5mm |
| Type of start | start with torque control (current limited to 3.5 In) |
| Maximum switching current | 2 A 30 V DC inductive 7 ms relay outputs |
| Height | 356mm |
| Width | 150mm |
| Operating altitude | > 1000...< 2000 m with current derating of 2.2 % per additional 100 m |
| Type of cooling | forced convection |
| [Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz |
| Discrete output number | 2 |
| Marking | CE |
| Standards | IEC 60947-4-2 |
| Product certifications | CCC |
| Brand Name | Schneider Electric |
| Supply frequency | 50...60 Hz - 10...10 % |
| Utilisation category | AC-53A |
| Discrete input type | (LI1- LI2- LI3) logic- 5 mA 4.3 kOhm |
| Net weight | 18 kg |
| Transmission rate | 4800- 9600 or 19200 bps |
| Physical interface | RS485 multidrop |
| Product or component type | soft starter |