Description
Schneider Electric LU2MB0BL Reverser block, TeSys Ultra, 38A, 690VAC, 24VDC coil, for vertical mounting
TeSys U reversing module for vertical mounting, for the constitution of TeSys U reversing starter controllers. It provides reverse power contacts, coil control with interlocking capabilities to be supplied with 24V DC. To be used with an advanced power base LUB120, LUB320, or LUB380 equipped with a Control Unit LUC*BL type. To be associated with an assembling connector LU9MR1C and a control terminal block LU9M1 to complete the vertical mounting. Green Premium compliant (RoHS/REACh).
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
| Resistance to fast transients | 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| Depth | 105mm |
| Ambient air temperature for operation | -25-70 °C with LUCA- LUCB- LUCC- LUCD |
| Fire resistance | 650 °C conforming to IEC 60695-2-12 |
| Resistance to electrostatic discharge | 8 kV level 4- on contact conforming to IEC 61000-4-2 |
| Current consumption | 120 mA at 24 V DC I rms sealed |
| Supplier Code | LU2MB0BL |
| Ambient air temperature for storage | -40-85 °C |
| Height | 80mm |
| Network frequency | 40...60 Hz |
| Width | 45mm |
| Vibration resistance | 4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27 |
| Operating altitude | 2000 m |
| Resistance to radiated fields | 10 V/m level 3 conforming to IEC 61000-4-3 |
| Operating time | 75 ms without change of direction |
| [Uc] control circuit voltage | 24 V DC |
| Device short name | LU2MB |
| Compatibility code | LU2MB |
| Shock resistance | 15 gn power poles closed conforming to IEC 60068-2-27 |
| Fixing mode | plug-in |
| Device application | motor control |
| [Ue] rated operational voltage | 690 V AC power circuit |
| [Ui] rated insulation voltage | 600 V conforming to CSA C22.2 No 60947-4-1 |
| IP degree of protection | IP20 conforming to IEC 60947-1 (other faces) |
| Range | TeSys |
| Standards | CSA C22.2 No 60947-4-1- with phase barrier |
| Product certifications | ASEFA |
| Brand Name | Schneider Electric |
| Device mounting | direct mounting |
| Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
| Inrush restraint duration | 15 ms DC |
| Protective treatment | TH conforming to IEC 60068 |
| Tightening torque | power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6mm |
| Net weight | 0.4 kg |
| [Ie] rated operational current | 38 A |
| Product or component type | reverser block |
| Connections - terminals | power circuit: screw clamp terminals 1 cable(s) 2.5-10mm² (external diameter: 4mm) flexible without cable end |
We would love your opinion
Was the information on this page helpful?
Thanks for your feedback!