Schneider A9D32640, Residual current breaker with overcurrent protection (RCBO), Acti9 INDPN N Vigi, 1P+N C curve, 40A, 30mA.
Schneider A9D32640, This Acti9 iDPN Vigi is a modular residual current breaker with overcurrent protection (RCBO). It has 2P with 1 protected pole, 40A rated current and C tripping curve. This A type device has 30mA sensibility. Breaking capacity at 230VAC is 6000A according to IEC 61009-1.
Features:
• Protects against short circuits, cable overloads, electric shocks from indirect contact and fire hazards.
• Provides a safe and reliable solution for commercial and industrial applications.
• Complies with the EN/IEC 61009-2-1 standard.
• The frequency is 50Hz.
•It is DIN rail mountable.
• Offers 2 VisiTrip windows to reduce intervention time and VisiSafe for a safe intervention.
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Poles | 1P + N |
Relative humidity | 95-95 % at 55-55 °C |
Number of protected poles | 1 |
Electromagnetic compatibility | 8/20 µs impulse withstand- 250 A conforming to EN/IEC 61009-2-1 |
Residual current tripping technology | voltage independent |
Ambient air temperature for operation | -25-60 °C |
[Ics] rated service breaking capacity | 6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Earth-leakage protection | integrated |
Mounting mode | clip-on |
Comb busbar and distribution block compatibility | top or bottom: YES |
Supplier Code | A9D32640 |
Earth-leakage sensitivity | 30 mA |
Ambient air temperature for storage | -40-85 °C |
Network frequency | 50 Hz |
Neutral position | left |
9 mm pitches | 4 |
Warranty | 18 months |
Network type | AC |
Control type | toggle |
IP degree of protection | IP40 (modular enclosure) conforming to IEC 60529 |
Range | Acti9 |
Weight | 125g |
Overvoltage category | III conforming to IEC 60364 |
Curve code | C |
Electrical durability | 10000 cycles |
Local signalling | ON- OFF- fault trip |
Pollution degree | 3 |
Tightening torque | 2-2 N.m top or bottom |
Market segment | small commercial |
Earth-leakage protection class | type A |
Connections - terminals | single terminal top or bottom 1-10mm² flexible |
Contact position indicator | yes |
Suitability for isolation | yes conforming to EN/IEC 60947-2 |
[In] rated current | 40 A |
Earth-leakage protection time delay | instantaneous |
Depth | 73mm |
Connection pitch | 9mm between phase and neutral |
Colour | White |
Mounting support | DIN rail |
Power losses per pole | 10.4 W |
Rated breaking and making capacity | Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Mechanical durability | 20000 cycles |
Breaking capacity | 6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
Height | 85mm |
Limitation class | 3 conforming to EN/IEC 61009-2-1 |
Poles description | 1P + N |
Width | 36mm |
Wire stripping length | 15mm for top or bottom connection |
Device short name | iDPN N Vigi |
Tropicalisation | 2 conforming to IEC 60068-1 |
Compatibility code | iDPN |
Trip unit technology | thermal-magnetic |
Device application | distribution |
[Ue] rated operational voltage | 230...240 V AC 50 Hz |
Device location in system | outgoer |
[Ui] rated insulation voltage | 400 V AC 50 Hz |
Standards | EN/IEC 61009-2-1 |
Product certifications | RCM |
Brand Name | Schneider Electric |
[Uimp] rated impulse withstand voltage | 4 kV |
Product name | Acti9 iDPN Vigi |
Magnetic tripping limit | 5...10 x In |
Locking options description | padlocking device |
Net weight | 125 g |
Product or component type | residual current breaker with overcurrent protection (RCBO) |