Description
This Acti9 iPRD40r surge arrester protects 3P+N installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level in incoming panel board. It offers remote reporting of the "cartridge must be changed" message. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. It is compatible with TT and TN-S earthing system. The Imax rated discharge current is 40kA. The In nominal discharge current is 15kA. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC. The Up Voltage protection level is 1.4kV in common mode (N/PE) and in differential mode (L/N). The Un rated service voltage is 230VAC or 400VAC. The operating frequency is 50Hz or 60Hz. The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The width in 9mm pitches is 8. The weight is 450g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.
⢠Suitable for TT and TN-S networks with high prospective short-circuit fault currents
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Remote signalling | with |
Relative humidity | 5-95 % |
Surge arrester technology | MOV + GDT |
Surge arrester class type | type 2 |
Depth | 69mm |
Ambient air temperature for operation | -25-60 °C |
Colour | White |
Mounting mode | clip-on (DIN rail) |
Signal contacts composition | 1 SD (1 C/O) |
Supplier Code | A9L40601 |
Ambient air temperature for storage | -40-85 °C |
GrosWeight | 452 g |
Height | 85mm |
Poles description | 3P + N |
Width | 72mm |
Operating altitude | 2000 m |
Maximum [Up] voltage protection level | differential mode <1.4 kV type 2 L/N |
9 mm pitches | 8 |
Maximum discharge current | differential mode: 40 kA L/N |
Quality labels | NF |
Warranty | 18 months |
Device short name | iPRD40r |
Compatibility code | iPRD40r |
Earthing system | TN-S |
Device application | distribution |
[Ue] rated operational voltage | 230/400 V AC (+/- 10 %) at 50/60 Hz |
Residual current | 0.003 mA |
Range | Acti9 |
Standards | IEC 61643-11:2011 |
Surge arrester type | electrical distribution network |
Brand Name | Schneider Electric |
Product certifications | CE |
[Uc] maximum continuous operating voltage | common mode: 350 V L/PE |
Disconnector device type | associated circuit breaker IC60N 40 A curve C - Icu 10 kA |
Length | 9.3 cm |
Volume | 617.52 cm3 |
Signalling circuit voltage | 0.25 A/250 V AC 50/60 Hz |
Product name | Acti9 iPRD |
Tightening torque | 2.5-2.5 N.m |
Net weight | 0.421 kg |
IK degree of protection | IK03 conforming to IEC 62262 |
[Ut] temporary overvoltage | 1453 V L/PE 200 ms safe failure mode |
Nominal discharge current | common mode: 15 kA (N/PE) |
Product or component type | surge arrester with pluggable cartridge |
Connections - terminals | tunnel type terminal (upside) 2.5-35mm² |