Description
Schneider LRD350 TeSys, TeSys Deca, Thermal overload relay, 690VAC, 37 to 50A, 1NO+1NC, class 10A, EverLink BTR screw
TeSys LRD thermal overload relay, 65A/690V, thermal setting range 48-65A, tripping class 10A, for protection of 3-phase motors 30kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals , it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Mount | Plate, with specific accessories |
Thermal overload class | class 10A conforming to IEC 60947-4-1 |
Ambient air temperature for operation | -20-60 °C without derating conforming to IEC 60947-4-1 |
Current Type | AC |
Supplier ref | LRD365 |
Contactor | LC1D50A, LC1D65A |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
Supplier Code | LRD365 |
Ambient air temperature for storage | -60-70 °C |
Trip Class | Class 10A |
Permissible current | 0.06 A at 440 V DC-13 for signalling circuit |
Network frequency | 0...400 Hz |
Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
Network type | AC |
Terminal Type | Screw Clamp |
Control type | blue push-button: reset |
IP degree of protection | IP20 conforming to IEC 60529 |
Range | TeSys Deca |
Flame retardance | V1 conforming to UL 94 |
Weight | 0.375 kg |
Frequency Rating | 0 - 400 Hz |
Item Name | Overload Relay |
Tightening torque | power circuit: 5 N.m - on EverLink BTR screw connectors |
Thermal protection adjustment range | 48-65 A |
Auxiliary contact composition | 1 NO + 1 NC |
Current | 48 - 65A |
Connections - terminals | control circuit: screw clamp terminals 2 cable(s) 1-2.5mm² solid without cable end |
Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Associated fuse rating | 4 A BS for signalling circuit |
Standard | CSA, UL Listed |
Depth | 123mm |
Mounting support | under contactor |
Climatic withstand | conforming to IACS E10 |
Voltage | 690 V |
Degree of Protection | IP20 |
Height | 70mm |
Width | 55mm |
Temperature Rating | -20 to 60 deg C |
Device short name | LRD |
Phase failure sensitivity | tripping current 130 % of Ir on two phase- the last one at 0 |
Compatibility code | LRD |
Product compatibility | LC1D50A |
Mechanical robustness | vibrations: 4 gn conforming to IEC 60068-2-6 |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
[Ui] rated insulation voltage | power circuit: 600 V conforming to UL |
Temperature compensation | -20-60 °C |
Standards | UL 60947-4-1 |
Product certifications | UL |
Brand Name | Schneider Electric |
EAN/UPC | 3389119215510 |
[Uimp] rated impulse withstand voltage | 6 kV |
Type | Thermal |
Reset Type | Manual/Automatic |
IP Rating | IP20 |
Product name | TeSys Deca |
Relay application | motor protection |
Frequency | 0...400 Hz |
Net weight | 0.375 kg |
Product or component type | differential thermal overload relay |
Have questions about this product?