NHP ARB2123STD Terasaki TemPower 2 AR ACB Body AR2 65kA 1250A 3P with AGR21CL and Shunt Trip
Code: NHPARB2123STD
Unit of measure:
EACH
Description
NHP ARB2123STD Terasaki TemPower 2 AR ACB Body AR2 65kA 1250A 3P with AGR21CL and Shunt Trip
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Max. altitude before derating | 2000m |
Frame size rating | 1250A |
Max. vibration acceleration | 0.7m/s² |
Electrical life at Un - In (service cycles) | 12000 cycles |
Short time withstand current Icw - 1 sec | 65kA |
Maximum operating temperature | 60°C |
Allowable relative humidity | 45-85 % |
Rated temperature | -5-60°C |
Rated impulse withstand voltage Uimp | 12kV |
Integrated earth fault protection | Yes |
Rated current In | 1250A |
Short time protection adjustment range | 1250-12500 A |
AC power loss per pole at In | 117 W |
Supplier Code | ARB2123STD |
Height | 490mm |
Built-in depth | 385mm |
Width | 354mm |
Type of electrical connection of main circuit | EV011047 - Connection at separate chassis part |
Rated insulation voltage Ui | 1000V |
Power loss | 350W |
Rated short circuit breaking capacity - Icu 690V AC | 50kA |
Rated short circuit breaking capacity - Ics 690V AC | 50kA |
Mechanical life (service cycles) | 15000 cycles |
Rated surrounding temperature without derating | 55°C |
Pole Configuration | 3 Pole |
Max. rated operation voltage Ue AC | 690V |
Weight | 53kg |
Brand Name | NHP |
Instantaneous protection adjustment range | 2500-20000 A |
ETIM Class | Power switching circuit breaker |
Long time overload protection adjustment range | 500-1250 A |
Trip curve | LSIG |
Pollution degree | 3 |
Rated frequency | 50-60 Hz |
Suitable for isolation | Yes |