Schneider LC1D12BNE Contactor, TeSys D, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 12A, 24-60VAC/DC coil
TeSys D contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3/3e (5.5kW@400V). It provides a low consumption 24-60V AC/DC coil with electronic control for direct PLC output connection, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Features:
• Reference contains Substances of Very High Concern above the threshold
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Contactor application | resistive load |
Hold-in power consumption in W | 0.6-0.6 W at 20 °C |
Maximum operating rate | 3600 cyc/h at 60 °C |
Non-overlap time | 1.5 ms on energisation between NC and NO contact |
Mount | Rail |
Minimum switching current | 5 mA for signalling circuit |
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 |
Signalling circuit frequency | 25...400 Hz |
[Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit |
Supplier Code | LC1D12BNE |
GrosWeight | 396.000 g |
Breaking Capacity | 250 A |
[Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit |
Warranty | 18 months |
Inrush power in W | 14-14 W (at 20 °C) |
Inrush power in VA | 15-15 VA 50/60 Hz (at 20 °C) |
Hold-in power consumption in VA | 0.9-0.9 VA 50/60 Hz (at 20 °C) |
Motor power kW | 5.5 kW at 415 V AC 50 Hz (AC-3e) |
Safety reliability level | B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Insulation resistance | > 10 MOhm for signalling circuit |
IP degree of protection | IP20 front face conforming to IEC 60529 |
Range | TeSys Deca |
Flame retardance | V1 conforming to UL 94 |
Weight | 0.373 kg |
Overvoltage category | III |
Electrical durability | 2.3 Mcycles 11 A AC-3e at Ue <= 440 V |
Volume | 649.800 cm3 |
Protective cover | with |
Pollution degree | 3 |
Tightening torque | control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 |
Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Auxiliary contact composition | 1 NO + 1 NC |
[Ie] rated operational current | 12 A (at <60 °C) at <= 440 V AC-3e for power circuit |
Connections - terminals | power circuit: screw clamp terminals 1 1-4mm² - cable stiffness: flexible without cable end |
Control circuit type | AC/DC at 50/60 Hz AC/DC electronic |
Associated fuse rating | 40 A gG at <= 690 V coordination type 1 for power circuit |
Depth | 86mm |
Mounting support | plate |
Pole contact composition | 3 NO |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Voltage | <= 690 V |
Mechanical durability | 15 Mcycles |
Permissible ambient air temperature around the device | 60-70 °C with derating |
Climatic withstand | conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
Coil technology | built-in bidirectional peak limiting |
Height | 77mm |
Minimum switching voltage | 17 V for signalling circuit |
Poles description | 3P |
Width | 45mm |
Operating altitude | 0...3000 m |
Operating time | 45...55 ms closing |
Device short name | LC1D |
[Uc] control circuit voltage | 24...60 V DC |
Compatibility code | LC1D |
Auxiliary contacts type | type mirror contact 1 NC conforming to IEC 60947-4-1 |
Mechanical robustness | vibrations contactor closed (4 Gn- 5...300 Hz) |
[Ue] rated operational voltage | power circuit: <= 690 V AC 25...400 Hz |
Pole Configuration | 3 Pole |
[Ui] rated insulation voltage | signalling circuit: 690 V conforming to IEC 60947-1 |
Standards | EN/IEC 60947-5-1 |
Control circuit voltage limits | 0.8...1.1 Uc (-40-60 °C):operational DC |
Product certifications | UKCA |
Brand Name | Schneider Electric |
Heat dissipation | 0.6-0.6 W at 50/60 Hz |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
Power dissipation per pole | 0.36 W AC-3 |
IP Rating | IP20 |
Length | 12.000 cm |
Motor power hp | 2 hp at 230/240 V AC 60 Hz for 1 phase motors |
Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
Utilisation category | AC-1 |
Net weight | 0.373 kg |
Product or component type | contactor |