Description
Motor Starter POWER BASE ONLY 3 Pole 12 Amp Max. 10kA @ 500V 1 NO + 1 NCTeSys Control Ultra motor starters Self-Protected Starter Base, With non removable screw terminations
Features:
• TeSys U standard power base, 3 poles (3NO), 12A/690V, to be completed with a control unit LUC to form a TeSys U starter controller, for 3-phase motor applications up to 5.5kW@400V.
• Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" starter controller with basic or advanced protection and control functions
• It is equipped with a control terminal block, and blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour.
• Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle.
• Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine)
Technical Specifications
Looking for something specific? Search with keywords to help filter your required specifications.
Maximum operating rate | 3600 cyc/h |
Safe separation of circuit | 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N |
Ambient air temperature for operation | -25-70 °C with LUCA- LUCB- LUCC- LUCD |
[Ics] rated service breaking capacity | 4 kA at 690 V |
Current Type | AC/DC |
[Ith] conventional free air thermal current | 12 A |
Supplier Code | LUB12 |
Ambient air temperature for storage | -40-85 °C |
Network frequency | 40...60 Hz |
Vibration resistance | 4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27 |
Resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
Non-dissipating shock wave | 2 kV common mode 48...220 V DC conforming to IEC 60947-6-2 |
Shock resistance | 15 gn power poles closed conforming to IEC 60068-2-27 |
Fixing mode | screw-fixed (plate) |
Safety reliability level | B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
IP degree of protection | IP20 conforming to IEC 60947-1 (other faces) |
Range | TeSys Control Ultra motor starters |
Immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
Mounting | Din Mount |
Item Name | Motor Starter Power Base |
Protective treatment | TH conforming to IEC 60068 |
Tightening torque | power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6mm |
Rated Current | 12 Amp Max. 10kA @ 500V |
Auxiliary contact composition | 1 NO + 1 NC |
Current | 12A |
[Ie] rated operational current | 12 A at 500 V |
Connections - terminals | control circuit: screw clamp terminals 2 cable(s) 0.75-1.5mm² rigid |
Category | Motor Starters & Drives |
Typical current consumption | 280 mA at 48...72 V DC I maximum while closing with LUCA- LUCB- LUCC- LUCD |
Resistance to fast transients | 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
Suitability for isolation | yes |
Depth | 126mm |
Fire resistance | 650 °C conforming to IEC 60695-2-12 |
Resistance to electrostatic discharge | 8 kV level 4 on contact conforming to IEC 61000-4-2 |
Mechanical durability | 15 Mcycles |
Voltage | 24 - 220 V AC/DC |
Height | 154mm |
Poles description | 3P |
Width | 45mm |
Operating altitude | 2000 m |
Operating time | 50 ms at >= 72 V closing with LUCA- LUCB- LUCC- LUCD for control circuit |
[Uc] control circuit voltage | 48...72 V DC |
Device short name | LUB |
Compatibility code | LUB |
Auxiliary contacts type | type mirror contact (1 NC) conforming to IEC 60947-1 |
Device application | motor protection |
[Ue] rated operational voltage | 690 V AC for power circuit |
[Ui] rated insulation voltage | 600 V conforming to CSA C22.2 No 60947-4-1 |
Standards | IEC 60947-6-2 |
Product certifications | CSA |
Brand Name | Schneider Electric |
Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
Heat dissipation | 1.7-1.7 W for control circuit with LUCM |
EAN/UPC | 3389110362770 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
Type | Non-Reversing |
Immunity to microbreaks | 3 ms for control circuit |
Contact Configuration | 1 NO + 1 NC |
Product name | TeSys Ultra |
Utilisation category | AC-41 |
Net weight | 0.9 kg |
Product or component type | non reversing power base |